Permit: T04CM04545

Parcel: 136287840


Addresses:

7452 E POINCIANA PL


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM04545

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
04/21/2005 FRAMING Approved IVRS - Inspection :*
04/20/2005 FRAMING Partial Approval IVRS - Inspection :*
1) NEED RED HEADS
04/19/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL RED HEADS IN GARAGE WEST WALL, FRONT DOOR, KITCHEN, SOUTH BEDROOM AND LIVING
2) SEAL BOTTOM PLATE/MESH GARAGE EAST WALL
3) SECURE WALL AT DRYER DUCT AND STOVE VENT
4) MOVE PEX FROM KITCHEN CAN LIGHT
5) PROTECT MAIN PEX RISER
6) REMOVE STAPLES BEHIND HOMERUNS