Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T04CM04545
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 03/09/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/24/2005 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) PLAN CALLS FOR H-3 HEADERS 3-2X8 AS SHOWN. 2) GIRDER TRUSS AT EAST BEDROOM APPEARS TO BE WRONG TYPE, NEED TRUSS SHOP DRAWINGS. 3) TRUSS TO GIRDER HANGERS USE 16 D COMMON NAILS PER HANGER CAT.4) NAIL ALL SHEAR PANELS WITH 8D SPOT NAILS, HORIZ JOINS. 5) DON'T LOAD ROOF. 6) FIND DETAIL FOR ATTACHING SHEAR WALL TO ROOF STRUCTURE ( TRANSFER) |