Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1) GAS PRESSURE TEST IS OK MINIMUM OF 50 POUNDS AS PER APPROVED SPECS 2) FUME HOOD GAS SUPPLY IS OK AS PER RED LINE |
|
| 05/24/2005 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 1) 50 PSI AIR TEST IN ENTIRE SYSTEM OK PENDING CORRECT PERM CAP WITH SEALS FOR VENTING SLEEVE AT INSTRUCTORS TABLE, CITY REVISED PLAN OF ADDITION OF 1/2" GAS TO FUME HOOD, CORRECT SUPPORTS AT STUB-OUTS IN SCIENCE LAB AND AT ALL DROPS AND CORRECT SUPPORTS OF ALL OVERHEAD PIPING |
|
| 05/19/2005 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 1) SOIL WATER TEST IS OK 2) OVERHEAD WATER DISTRIBUTION IS OK 3) ALL WELDED GAS PIPE AIR TEST 4) 60 POUNDS MINIMUM IS OK |