Permit: T04CM04534

Parcel: 13819045A

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
05/27/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) GAS PRESSURE TEST IS OK MINIMUM OF 50 POUNDS AS PER APPROVED SPECS
2) FUME HOOD GAS SUPPLY IS OK AS PER RED LINE
05/24/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) 50 PSI AIR TEST IN ENTIRE SYSTEM OK PENDING CORRECT PERM CAP WITH SEALS FOR VENTING SLEEVE AT INSTRUCTORS TABLE, CITY REVISED PLAN OF ADDITION OF 1/2" GAS TO FUME HOOD, CORRECT SUPPORTS AT STUB-OUTS IN SCIENCE LAB AND AT ALL DROPS AND CORRECT SUPPORTS OF ALL OVERHEAD PIPING
05/19/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) SOIL WATER TEST IS OK
2) OVERHEAD WATER DISTRIBUTION IS OK
3) ALL WELDED GAS PIPE AIR TEST
4) 60 POUNDS MINIMUM IS OK