Permit: T04CM04525

Parcel: 137050040

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/13/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/12/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- FINISH GAS INSTALL TO AC UNITS ON ROOF
- PROVIDE A DISCONNECT, CONDENSATE DRAIN & FRESH AIR INTAKE ON EXISTING A/C
- EXTEND WATER HEATER VENT 2' ABOVE WALL ON ROOF
- PROVIDE MIN. 3 SCREWS IN ALL JOINTS OF WATER HEATER VENT CONNECTORS.
- PROVIDE A HIGH COMBUSTION AIR VENT TO WATER HEATER ENCLOSURE.
03/27/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
EXTEND STAINLESS TO CEILING AT RIGHT HAND SIDE OF HOOD
SECURE ELEC DISCONNECT TO EVAP COOLER
PROVIDE ROMEX CONNECTOR ON POWER CORD
PROVIDE GREASE CUP OR EXHAUST FAN
PROVIDE QUICK DISCONNECTING GAS CONNECTOR & RESTRAINT FOR GRIDDLE.