Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04CM04525

Parcel: 137050040

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
07/13/2007 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection :*
11/07/2006 ELECTRIC - SERVICE RELOCATION Partial Approval IVRS - Inspection :*
10/31/2006 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/27/2006 ELECTRIC - SERVICE RELOCATION Partial Approval IVRS - Inspection :*
06/26/2006 ELECTRIC - SERVICE RELOCATION Partial Approval IVRS - Inspection :*
06/21/2006 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. GROUNDING AT SERVICE FOR BOND BUSHINGS STILL TO SMALL, USE 1/0 FOR 3"
2. USE SEALING LOCKNUT FOR CONNECTORS AT TOP OF GUTTER.
3. MULTI TERMINATION NOT APPROVED IN ONE LUG.
06/16/2006 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. BOND WATER & GAS PIPING
2. GROUND WIRE TO SMALL IN GUTTER, BOND JUMPERS SIZE PER 250 NEC.
3. DO NOT TERMINATE MORE THAN ONE WIRE PER LUG UNLESS LISTED FOR SUCH.
4. INSTALL BOND SCREWS IN DISCONNECTS AT SERVICE FOR NEUTRAL.
5. STRAP BARE GROUND TO WALL OF BUILDING.
6. LB COVERS MISSING.
06/14/2006 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
NOTES:
1. NO COMPLIANCE WITH NOTE #2 & #3
2. NEUTRAL MUST BE BONDED AT SERVICE PER ART. 250 NEC
3. WRONG COLOR OF PHASE TAPE ON CONDUCTOR AT SERVICE IMPROPER GROUND CLAMP AT SECOND GROUND ROD.
4. INSTALL BUSHING AT 2" CONDUIT TERM. INTO PANEL.
06/06/2006 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. PROVIDE PLANS/PERMIT OK
2. GROUNDING OF SERVICE NOT PER PLAN, 600 MCM CONDUCTOR CANNOT BE CUT TO REDUCE SIZE TO FIT INTO 250 MCM LUG IN METER BASE -- USE APPROVED LUGS.
3. BONDING TYPE BUSHINGS REQUIRED ON NIPPLES AHEAD OF OVERCURRENT DEVICES - BOND NEUTRAL AT DISCONNECT SWITCHES PER NEC ART. 250
4. BOND WATER & GAS
5. OPEN GUTTER FOR INSPECTION.
6. LEAVE NAME & PHONE # OF LICENSED CONTR. DOING WORK OR CALL DAN OR RAY MAJUTA AT 791-5550 EXT. 1136
7. 6'7" MAX. HEIGHT TO HIGHEST BREAKER.
8. REMOVE BOND LINK NEUTRAL TO GROUND BAR AT INSIDE PANEL.