Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2007 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 11/07/2006 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :* | |
| 10/31/2006 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/27/2006 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :* | |
| 06/26/2006 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :* | |
| 06/21/2006 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. GROUNDING AT SERVICE FOR BOND BUSHINGS STILL TO SMALL, USE 1/0 FOR 3" 2. USE SEALING LOCKNUT FOR CONNECTORS AT TOP OF GUTTER. 3. MULTI TERMINATION NOT APPROVED IN ONE LUG. |
|
| 06/16/2006 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. BOND WATER & GAS PIPING 2. GROUND WIRE TO SMALL IN GUTTER, BOND JUMPERS SIZE PER 250 NEC. 3. DO NOT TERMINATE MORE THAN ONE WIRE PER LUG UNLESS LISTED FOR SUCH. 4. INSTALL BOND SCREWS IN DISCONNECTS AT SERVICE FOR NEUTRAL. 5. STRAP BARE GROUND TO WALL OF BUILDING. 6. LB COVERS MISSING. |
|
| 06/14/2006 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES: 1. NO COMPLIANCE WITH NOTE #2 & #3 2. NEUTRAL MUST BE BONDED AT SERVICE PER ART. 250 NEC 3. WRONG COLOR OF PHASE TAPE ON CONDUCTOR AT SERVICE IMPROPER GROUND CLAMP AT SECOND GROUND ROD. 4. INSTALL BUSHING AT 2" CONDUIT TERM. INTO PANEL. |
|
| 06/06/2006 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. PROVIDE PLANS/PERMIT OK 2. GROUNDING OF SERVICE NOT PER PLAN, 600 MCM CONDUCTOR CANNOT BE CUT TO REDUCE SIZE TO FIT INTO 250 MCM LUG IN METER BASE -- USE APPROVED LUGS. 3. BONDING TYPE BUSHINGS REQUIRED ON NIPPLES AHEAD OF OVERCURRENT DEVICES - BOND NEUTRAL AT DISCONNECT SWITCHES PER NEC ART. 250 4. BOND WATER & GAS 5. OPEN GUTTER FOR INSPECTION. 6. LEAVE NAME & PHONE # OF LICENSED CONTR. DOING WORK OR CALL DAN OR RAY MAJUTA AT 791-5550 EXT. 1136 7. 6'7" MAX. HEIGHT TO HIGHEST BREAKER. 8. REMOVE BOND LINK NEUTRAL TO GROUND BAR AT INSIDE PANEL. |