Permit: T04CM04525

Parcel: 137050040

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/13/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/13/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK WALLS & CEILINGS
- SUPPORT 2" CONDUIT SECURELY ON HOLE STRAPS NOT INSTALLED PROPERLY.
11/07/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL ONLY - STRAP ROMEX IN CEILING PER CODE WITHIN 12" CHECK & TIGHTEN ALL FITTINGS ON CONDUIT.
10/31/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ROMEX MUST BE SUPPORTED WITHIN 12" EACH TERMINATION.
2. CONNECTOR NOT CONNECTED IN GUTTER ABOVE CEILING IN NEW CONST. AREA.
3. ALL J-BOXES MUST BE ACCESSIBLE IN CEILING AREAS.
4. USE OF CHASE NIPPLES NOT ALLOWED IN PANELS.
5. ALL CONDUITS MUST BE SUPPORTED PER CODE.
6. ROUND BOXES CAN ONLY HAVE ONE CABLE PER BOX
PLUG UNUSED OPENINGS.
06/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CONTRACTOR TO MAKE SURE POWER TO CONSTRUCTION AREA IS NOT TO BE ENERGIZED WITHOUT APPROVAL FOROM INSPECTOR
06/26/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BOND NEUTRAL IN GUTTER TO GROUND, USE PROPER SIZE WIRE-ALSO PER NOTE 6/14/06 #2
2) TIGHTEN NIPPLE BETWEEN GUTTER AND METER