Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/13/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK WALLS & CEILINGS - SUPPORT 2" CONDUIT SECURELY ON HOLE STRAPS NOT INSTALLED PROPERLY. |
|
| 11/07/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL ONLY - STRAP ROMEX IN CEILING PER CODE WITHIN 12" CHECK & TIGHTEN ALL FITTINGS ON CONDUIT. |
|
| 10/31/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ROMEX MUST BE SUPPORTED WITHIN 12" EACH TERMINATION. 2. CONNECTOR NOT CONNECTED IN GUTTER ABOVE CEILING IN NEW CONST. AREA. 3. ALL J-BOXES MUST BE ACCESSIBLE IN CEILING AREAS. 4. USE OF CHASE NIPPLES NOT ALLOWED IN PANELS. 5. ALL CONDUITS MUST BE SUPPORTED PER CODE. 6. ROUND BOXES CAN ONLY HAVE ONE CABLE PER BOX PLUG UNUSED OPENINGS. |
|
| 06/27/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CONTRACTOR TO MAKE SURE POWER TO CONSTRUCTION AREA IS NOT TO BE ENERGIZED WITHOUT APPROVAL FOROM INSPECTOR |
|