Permit: T04CM04515

Parcel: 10511040A


Addresses:

4270 N ORACLE RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04CM04515

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/08/2005 PLUMBING - FINAL Approved IVRS - Inspection :* 1) CORRECTONS MADE OK. 2) PLUMBING FINAL OK. OK FOR C OF O PENDIN ANY OTHER INSPECTIONS
06/03/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* / 1) SUPPLY PIPING TO FIXTURES/APPLIANCES SHALL BE FULL SIZE, HARD PIPED. 2) RPZ'S LOCATED OVER 5' FROM FLOOR SHALL HAVE ACCESS. 3) HOT WTR PIPING NOT INSULATED IN MECH RM. 4) ALL SINKS REQUIRE CLEAN OUTS.
05/25/2005 PLUMBING - FINAL Partial Approval 1. SEWER/HCS APPROVED 012605 BY R MYERS
2. WALK THRUR WITH PLUMBER CONTRACTOR REQUESTING TEMP C OF O MINOR PLUMBING CORRECTIONS OK FOR TEMP C OF O STOI AND STEVE LONG
3. NO WATER AT THEIS TIME AWAITING APPROVAL OF PRIVATE SEWER
05/22/2005 PLUMBING - FINAL Partial Approval IVRS - Inspection :*