Permit: T04CM04503

Parcel: 140376710


Addresses:

6919 S HARRIER LP

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
05/05/2005 BUILDING - FINAL Approved IVRS - Inspection :*
05/04/2005 BUILDING - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) GROUND LUG IN ELECTRIC SERVICE NOT TORQUED TO 50 IN POUNDS
2) GAS BOND LUG IN ELECTRIC SERVICE NOT TORQUED TO 50 IN POUNDS
3) GAS BOND CLAMP CANNOT BE ENCASED IN STUCCO
4) A/C WHIP NOT CONNECTED
5) BARE WIRES BY A/C
6) STOPPED INPSECTION TO MANY ITEMS
7) NEXT FAILURE WILL BE CHARGED A REINSPECTION FEE