Permit: T04CM04492

Parcel: 125081090


Addresses:

35 N TUCSON BL


Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Permit Number - T04CM04492

Inspection Description - PLUMBING - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
10/22/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
10/22/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/PLUMBING FINAL OK. CONTRACTOR TO STRAP PIPE AS REQ'D. ABANDONED W.C. TO BE CAPPED OFF. OK FOR C/O PENDING ANY OTHER INSPECTION
10/19/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/1)NOT INSTALLED PER PLAN. WET VENTING IS LIMITED TO VERTICAL DRAINAGE PIPING 2)TRAP ARM LENGTH IS RESTRICTED TO 5 FEET. ONLY ONE TRAP ON A TRAP ARM. VENT TO BE DOWN STREAM OF TRAP 3)PLUMBER TO BE ON SITE AT TIME OF NEXT INSPECTION. WHERE ARE THE HAIR TRAPS?
10/19/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)INSTALL PER YOUR APPROVED PLAN. WASTE & VENT SYSTEM 2)ONLY (1) TRAP ALLOWED ON TRAP ARM. 3)YOU CANNOT REDUCE DRAINAGE PIPING IN SIZE 4)CLEANOUT FITTING IS TO BE USED ON VERTICAL DRAINAGE 5)NO HUB COUPLINGS ARE NOT APPROVED FOR USE ON ABS PIPE 6)CORRECTLY CAP ANY UNUSED PLUMBING DRAINAGE PIPING