Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
Permit Number - T04CM04492
Inspection Description - PLUMBING - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/22/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
10/22/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/PLUMBING FINAL OK. CONTRACTOR TO STRAP PIPE AS REQ'D. ABANDONED W.C. TO BE CAPPED OFF. OK FOR C/O PENDING ANY OTHER INSPECTION | |
10/19/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/1)NOT INSTALLED PER PLAN. WET VENTING IS LIMITED TO VERTICAL DRAINAGE PIPING 2)TRAP ARM LENGTH IS RESTRICTED TO 5 FEET. ONLY ONE TRAP ON A TRAP ARM. VENT TO BE DOWN STREAM OF TRAP 3)PLUMBER TO BE ON SITE AT TIME OF NEXT INSPECTION. WHERE ARE THE HAIR TRAPS? | |
10/19/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)INSTALL PER YOUR APPROVED PLAN. WASTE & VENT SYSTEM 2)ONLY (1) TRAP ALLOWED ON TRAP ARM. 3)YOU CANNOT REDUCE DRAINAGE PIPING IN SIZE 4)CLEANOUT FITTING IS TO BE USED ON VERTICAL DRAINAGE 5)NO HUB COUPLINGS ARE NOT APPROVED FOR USE ON ABS PIPE 6)CORRECTLY CAP ANY UNUSED PLUMBING DRAINAGE PIPING |