Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM04478
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/11/2005 | FRAMING | Approved | IVRS - Inspection :* | |
04/10/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) SEE CLIP NOTES 2) ADD BLOCKS TO CARRY LOAD OF GIRDER TRUSS THRU FLOOR ON EAST SIDE OF HOUSE 3) OK TO INSULATE 4) AS CURRENTLY INSTALLED, H20 B-VENT WILL NEED TO EXTEND ABOVE 2ND FLOOR ROOF AT FINAL |
|
04/06/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) CHECK NAILING OF ALL HIP HANGERS 2) ADD HANGER N.E. HIP 3) FIRE BLOCK TUB 4) NAIL STRAP STOVE WIRE AT TOP PLATE 5) PENDING COMPLETION OF STUCCO MESH 6) HORIZONTAL (30 DEGREE) RUN OF WATER HEATER B-VENT CANNOT EXCEED 75 PERCENT OF VERTICAL RUN |