Permit: T04CM04465

Parcel: 138041720


Addresses:

702 W CALLE LERDO

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
12/27/2004 BUILDING - FINAL Approved IVRS - Inspection :*
12/23/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 12 GAUGE WIRE REQUIRED ON 20 AMP CIRCUIT OR CHANGE CIRCUIT BREAKERS TO 15 AMP FOR THESE CIRCUITS
2) SPLICED GROUNDS REQUIRE A WIRE NUT OR BUCANNON
3) WIRE BOXES FROM GROUND WIRE TO GROUND SCREW ON BOX THEN TO GROUND ON DEVICE LIKE NORTH WEST BOX