Permit: T04CM04456

Parcel: 12909146C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM04456

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/19/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/04/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*TEMP C/O NOTES: 1) INSTALL APPROVED PERMANENT PANEL SCHEDULE. 2) INSTALL DISCONNECTS FOR INSTALL HOT HEATERS, OR A LOCKOUT DEVICE ON BREAKERS CAPABLE OF BEING LOCKED IN THE OH POSITION. PER NEC 422-31. OK FOR TEMP C OF O
04/01/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*1) NOT ALL FIXTURES HAVE 2 ?? TIES, ALSO LAY INS NEED TO BE SCREWED OR CLIPPED. 2) FLEX CONDUIT IN CEILING HAS TO BE SUPPORTED OF T-BAR 3) COMMUNICATIONS & LV WIRING ALSO HAS TO BE SUPPORTED OF T-BAR. 4) PANEL L HAS TO BE ACCESSIBLE TO THIS OCCUPANCY FOR BEING ABLE TO ACCESS OVERCURRENT DEVICES, THE PANEL IS IN ANOTHER SPACE. LETTER OK. 5) NEED ACCESS TO ROOF TO CK AC'S. 6) INSTALL FUSES.