Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM04456
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/19/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/04/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*TEMP C/O NOTES: 1) INSTALL APPROVED PERMANENT PANEL SCHEDULE. 2) INSTALL DISCONNECTS FOR INSTALL HOT HEATERS, OR A LOCKOUT DEVICE ON BREAKERS CAPABLE OF BEING LOCKED IN THE OH POSITION. PER NEC 422-31. OK FOR TEMP C OF O | |
04/01/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*1) NOT ALL FIXTURES HAVE 2 ?? TIES, ALSO LAY INS NEED TO BE SCREWED OR CLIPPED. 2) FLEX CONDUIT IN CEILING HAS TO BE SUPPORTED OF T-BAR 3) COMMUNICATIONS & LV WIRING ALSO HAS TO BE SUPPORTED OF T-BAR. 4) PANEL L HAS TO BE ACCESSIBLE TO THIS OCCUPANCY FOR BEING ABLE TO ACCESS OVERCURRENT DEVICES, THE PANEL IS IN ANOTHER SPACE. LETTER OK. 5) NEED ACCESS TO ROOF TO CK AC'S. 6) INSTALL FUSES. |