Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 05/18/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STOVE ANTI-TIP NOT INSTALLED 2) T & P AT WATER HEATER MUST BE HARD PIPE 3) SEAL ALL PENETRATIONS AT GARAGE 4) ALL BEDROOM SWITCHES OUTLETS AND SMOKE DETECTORS MUST BE ON ARC FAULT 5) HOSE BIB MISSING ANTI-SIPHON DEVICE 6) MARK HEATER MODEL 7) T & P CANNOT DISCHARGE ON PATIO |