Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM04443
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/05/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) WH SWITCHES TO BE 30 AMP |
|
07/25/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TO CLEAR #5 FOR ECO |
|
07/12/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK CLEAR FOR TEMP POWER | |
06/29/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
06/23/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service entrance is not per code.| 215* 1. UNITS LOCKED. 2. THE SERVICE DISCONNECTS EXCEED THE MAX HEIGH SET BY NEC 404.8. 3) THE TELEPHONE POST/ TERMINAL MUST BE MOVE OR REMOVED FROM FRONT OF ELECTRIC SERVICE EQUIPMENT SEE NEC 110.26 |
|
05/26/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK FOR METER SET 2) OK TO CLEAR METER AND POWER |