Permit: T04CM04443

Parcel: 125071810

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/08/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/05/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) WH SWITCHES TO BE 30 AMP
07/25/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK TO CLEAR #5 FOR ECO
07/12/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* OK CLEAR FOR TEMP POWER
06/29/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/23/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The service entrance is not per code.| 215* 1. UNITS LOCKED. 2. THE SERVICE DISCONNECTS EXCEED THE MAX HEIGH SET BY NEC 404.8. 3) THE TELEPHONE POST/ TERMINAL MUST BE MOVE OR REMOVED FROM FRONT OF ELECTRIC SERVICE EQUIPMENT SEE NEC 110.26
05/26/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK FOR METER SET
2) OK TO CLEAR METER AND POWER