Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/02/2004 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection :*/RELOCATE DUCT SMOKE DETECTORS AHEAD OF ALL RETURN DUCTS. LABEL FAN COILS & HEAT STRIPS. WHERE IS CONDENSATE DRAIN LINE TERMINATION? WILL CHECK CORRECTIONS OF FINAL. OK FOR CEILING TILES - LEAVE OUT AROUND FAN COILS |