Permit: T04CM04427

Parcel: 12801005H

Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Permit Number - T04CM04427

Inspection Description - SHEET ROCK NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/26/2004 SHEET ROCK NAILING Approved IVRS - Inspection :*
10/25/2004 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*/ 1) NORTH STOREROOM WALL-FITTING ROOM
10/22/2004 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
10/18/2004 SHEET ROCK NAILING Partial Approval IVRS - Inspection :FIRE RATED WALLS ARE REQUIRED TO BE CONSTRUCTED WITH TIGHT JOINTS
USG REQUIRES 1/8" MAX BETWEEN SHEETROCK ICBO REQUIRES 1/16" MAX FOR A TIGHT JOINT
YOUR WEST WALL IS NOT PROPERLY CONSTRUCTED
10/15/2004 SHEET ROCK NAILING Partial Approval IVRS - Inspection :NOTE: EAST DEMISING WALL IS NOTED AS EXISTING
PLEASE HAVE PARK MALL MGMT PROVIDE PERMIT THAT ALLOWED THEM TO BUILD THAT WALL
ALSO - MAINTAIN 1 HOUR SEPERATION AS REQUIRED BY IBC, BOTH SIDES OF WALL MUST BE SHEETROCKED