Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM04407
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/13/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
01/10/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AT PANEL AT BLDG - NEC 250.8 - SHEET METAL SCREWS NOT TO BE USED TO CONNECT GROUNDS TO ENCLOSURES, SCRAPE PAINT BEHIND & SEAL 1/2" HOLE. 2. SPLICING AT J-BOX BY BRIDGE TO BE WEATHERPROOF 3. UNABLE TO OPEN COVERS AT POLE BASES TO INSPECT 4. PROVIDE PLAN SHOWING ACCEPTABLE FIXTURES |