Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date |
Description |
Inspector |
Results |
Comments |
| 02/07/2005 |
MECHANICAL - HOODS |
|
Approved |
|
| 02/04/2005 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection :* YOU CANNOT USE A PLASTIC COVERING ON THE WALL WITHIN 18'' OF THE HOOD. PROVIDE COOLER DRAIN. NEED TO TEST DUCT SMOKE DETECTORS |
| 02/01/2005 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection :* DO NOT USE DIFFERENT MANUFACTURERS FIRE WRAP ON THE SAME SYSTEM. BE SURE WRAP UP INDSIDE CURB IS BANDED CORRECTLY. PROVIDE 18" FROM COMBUSTIBEL AT SIDE OF HOOD. |
| 01/26/2005 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection :* INSPECTED GREASE DUCT. OK TO FIRE WRAP |