Permit: T04CM04397

Parcel: 136261300

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
02/07/2005 MECHANICAL - HOODS Approved
02/04/2005 MECHANICAL - HOODS Partial Approval IVRS - Inspection :* YOU CANNOT USE A PLASTIC COVERING ON THE WALL WITHIN 18'' OF THE HOOD. PROVIDE COOLER DRAIN. NEED TO TEST DUCT SMOKE DETECTORS
02/01/2005 MECHANICAL - HOODS Partial Approval IVRS - Inspection :* DO NOT USE DIFFERENT MANUFACTURERS FIRE WRAP ON THE SAME SYSTEM. BE SURE WRAP UP INDSIDE CURB IS BANDED CORRECTLY. PROVIDE 18" FROM COMBUSTIBEL AT SIDE OF HOOD.
01/26/2005 MECHANICAL - HOODS Partial Approval IVRS - Inspection :* INSPECTED GREASE DUCT. OK TO FIRE WRAP