Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T04CM04389
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/17/2005 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) PLEASE BOND WATER TO INTERIOR SIDE OF SHUT OFF VALVE. 2) TIGHTEN LOOSE FITTING TO A/C UNIT. 3) FINISH #3 OF PREVIOUS INSPECTION. IS BONDING CONDUCTOR GOING TO BE BURIEDC OR STRAPED TO BUILDING? | |
| 05/04/2005 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) AN APPROVED FITTING IS NEEDED AT HOOD 2) MAINTAIN RECEPTACLE SPACING AS PER CODE AND PLANS 3) WHERE IS LIGHT OVER SINK AS PER PLANS 4) SMOKE DETECTOR TO BE INSTALLED PER MANUFACTURERS INSTRUCTIONS 8' FROM A DUCT 5) A DISCONNECTING MEANS IS NEEDED FOR WATER HEATER 6) PLEASE FILL REMAINING UNUSED OPENING IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT 7) BOND BOTH GAS SERVICES 8) PLEASE VERIFY WATER BOND 9) INSTALL A/C UNIT |