Permit: T04CM04389

Parcel: 121120110

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04CM04389

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/27/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :* OK ROUGH ELECT
01/25/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* PARTIAL OK TO COVER ALL BUT KITCHEN EAST WALL. 1) THE KITCHEN ELECTRICAL PLAN SHOWS A GFI RECEPTACLE ON EACH SIDE OF THE SINK NOW YOU HAVE A RECEPTACLE AND SWITCH ( DISPOSAL ) IN ONE BOX ALMOST OVER THE SINK. MOVE DOUBLE GANG BOX ( RECEPTACLE & SWITCH ) TO THE NORTH ONE STUD SPACE AND ADD RECEPTACLE TO SOUTH SIDE OF SINK.
01/21/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) NEEDS MIN OF 6" OF CONDUCTOR LE? IN EACH J-BOX ( NOTE: AND MIN 3" OR CONDUCTOR AVAILABLE OUTSIDE OF J-BOX) PER NEC. 2) J-BOXES OVER FILLED 3) KITCHEN-DINING REQUIRES 20 AMP CIRCUITS ( # 14 WIRE TOO SMALL CHANGE TO # 12 ) 4) SECURE ?? CABLE PER N.E.C