Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM04389
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK ROUGH ELECT | |
| 01/25/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL OK TO COVER ALL BUT KITCHEN EAST WALL. 1) THE KITCHEN ELECTRICAL PLAN SHOWS A GFI RECEPTACLE ON EACH SIDE OF THE SINK NOW YOU HAVE A RECEPTACLE AND SWITCH ( DISPOSAL ) IN ONE BOX ALMOST OVER THE SINK. MOVE DOUBLE GANG BOX ( RECEPTACLE & SWITCH ) TO THE NORTH ONE STUD SPACE AND ADD RECEPTACLE TO SOUTH SIDE OF SINK. | |
| 01/21/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEEDS MIN OF 6" OF CONDUCTOR LE? IN EACH J-BOX ( NOTE: AND MIN 3" OR CONDUCTOR AVAILABLE OUTSIDE OF J-BOX) PER NEC. 2) J-BOXES OVER FILLED 3) KITCHEN-DINING REQUIRES 20 AMP CIRCUITS ( # 14 WIRE TOO SMALL CHANGE TO # 12 ) 4) SECURE ?? CABLE PER N.E.C |