Permit: T04CM04387

Parcel: 12110005D


Addresses:

4730 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/25/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/24/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* 1) PROTECT M/C CABLE AT SHALLOW STUDS PROTECT PVC CONDUIT AT BASE PLATE.
01/12/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/1)PROTECT FLEX & PVC CONDUIT AT STUDS 2)PLANS NOT CITY APPROVED FOR CHANGES
12/10/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROTECT M/C CABLE AT WOOD STUDS
12/02/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) RECEIVED LETTER FOR M/C USAGE
2) JUNCTION BOXES TO BE ACCESSIBLE HARD CEILING
11/23/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) NO MORE THAN 360 DEGREE IN A CONDUIT RUN
2) OK CANS KITCHEN #1, 2, 3 DISPLAY #105, MEDIA
3) OK CENTER SHORT WALLS
11/15/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) M/C CABLE TO BE SUPPORTED WITHIN 12" OF BOX
2) NEED A LETTER AUTHORIZING USE OF M/C CABLE
3) FINISH FRONT STORE FRONT
4) OK WALLS EXCEPT AS NOTED