Permit: T04CM04386

Parcel: 140323070

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM04386

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/10/2005 FRAMING Approved IVRS - Inspection :*
12/29/2004 FRAMING Partial Approval IVRS - Inspection :*
1) PENDING CITY OF TUCSON APPROVAL OF REVISIONS
2) OK TO CONTINUE
12/27/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO GAS TEST
2) NO TEST ON DWV'S
3) NAIL PROTECT
4) ELECTRIC WITHIN 1 1/4 FROM EDGE OF STUD
5) ATTIC ACCESS NOT PER PLAN LOCATION
6) PROVIDE TRUSS CHANGES FOR FURNACE AREA
7) PROVIDE APPROVED ENGINEER REPAIR FOR SHEAR AT KITCHEN
8) STOPPED INSPECTION
9) NEXT FAILURE WILL RESULT IN A REFEE
12/22/2004 FRAMING Cancelled IVRS - Ri canceled
12/15/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GAS GUAGE INOPERATIVE
2) NAIL PROTECT VENT AT MASTER BATH AND WATER LINES
3) PRIMARY CONDENSATE HAS NEGATIVE PITCH
4) SECURE SHOWER VALVE AND LINES
5) ROMEX AT BEDROOM 2 SWITCH NOT IN BOX
6) REPAIR SHEAR AT KITCHEN
7) GABLE VENT AND REAR WINDOW NOT COMPLETE
8) FRONT WINDOW MISSING, KITCHEN WINDOW MISSING
10/25/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) HOUSE AT PRE-SLAB STAGE