Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM04386
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2005 | FRAMING | Approved | IVRS - Inspection :* | |
12/29/2004 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PENDING CITY OF TUCSON APPROVAL OF REVISIONS 2) OK TO CONTINUE |
|
12/27/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO GAS TEST 2) NO TEST ON DWV'S 3) NAIL PROTECT 4) ELECTRIC WITHIN 1 1/4 FROM EDGE OF STUD 5) ATTIC ACCESS NOT PER PLAN LOCATION 6) PROVIDE TRUSS CHANGES FOR FURNACE AREA 7) PROVIDE APPROVED ENGINEER REPAIR FOR SHEAR AT KITCHEN 8) STOPPED INSPECTION 9) NEXT FAILURE WILL RESULT IN A REFEE |
|
12/22/2004 | FRAMING | Cancelled | IVRS - Ri canceled | |
12/15/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GAS GUAGE INOPERATIVE 2) NAIL PROTECT VENT AT MASTER BATH AND WATER LINES 3) PRIMARY CONDENSATE HAS NEGATIVE PITCH 4) SECURE SHOWER VALVE AND LINES 5) ROMEX AT BEDROOM 2 SWITCH NOT IN BOX 6) REPAIR SHEAR AT KITCHEN 7) GABLE VENT AND REAR WINDOW NOT COMPLETE 8) FRONT WINDOW MISSING, KITCHEN WINDOW MISSING |
|
10/25/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) HOUSE AT PRE-SLAB STAGE |