Inspection History Details
Inspection Status: Approved
Inspection History: STUCCO MESH
Permit Number - T04CM04385
Inspection Description - STUCCO MESH
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/03/2005 | STUCCO MESH | Approved | IVRS - Inspection :* | |
01/19/2005 | STUCCO MESH | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL ALL PENETRATIONS, LATH NOT COMPLETE AT REAR GABLE, REAR TRANSAM AND BAT WINDOW 2) FIRE BLOCKS MISSING AT GARAGE WALL CHANNELS 3) DWV'S NEED TO BE TESTED ALL THE WAY TO TOP 4) PROVIDE 1" CLEARANCE AT B-VENT 5) PEX MUST BE 12" AWAY FROM CAN LIGHT 6) FIRE PLACE NOT FIRE BLOCKED 7) STOPPED INSPECTION |
|
01/18/2005 | STUCCO MESH | Not ready for Inspection | IVRS - Inspection :* |