Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM04383
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/22/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ONLY ONE CONDUCTOR PER TEMINAL/LOG. 2) DO NOT SPLIT NEUTRAL. 3) TERMINATE ALL GROUNDING EQUIPMENT CONDUCTORS. 4) USE BREAKERS LISTED FOR USE BY MANUFACTURER. 5) PLEASE REVISE CIRCUIT DIRECTORIES. 6) WE CANNOT HAVE OPEN JUNCTION BOX AND EXPOSED CONDUCTORS BEHIND BATH LIGHTS. PLEASE PROVIDE MANUFACTURERS INSTRUCTIONS FOR INSTALLATION. 7) FINISH ABOVE CEILING. 8) PLEASE CORRECT UNSAFE LIGHTING CONDITIONS ON ROOF OR REMOVE |