Permit: T04CM04372

Parcel: 112041140

Inspection Status: Partial Approval

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/09/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) OK TO COVER UNDERGROUND GAS LINES
2) RECALL FOR LINES IN ADDITION
06/06/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) ESTIMATED EXISTING FURNACE AT 50,000 BTU
2) 1" LINE OK TO HOUSE, EXCEPT FIRST SECTION OF PIPE (NEW LOCATION) TO BE 1 1/4"
3) USE TWO SEPERATE LINES FROM METER
4) EXISTING HOUSE: RANGE 65,000, FURN 50,000 ? AND H20 30,000 148,000 BTU=CFH 135
5) NEW GUEST HOUSE-SEE PLAN 19,000 BTU=CFH 173
6) LINE FT. FROM NEW METER TO KITCHEN 120' ??