Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM04368
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/29/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) SOIL WATER TEST IS OK. 2) P.O.C OF NEW BLDG DRAIN TO EXSISTING IS OK. 3) OVERHEAD WATER DISTRIBUTION IS OK | |
03/28/2005 | PLUMBING - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
03/23/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DOOR WAS LOCKED |
|
03/18/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) GAS PRESSURE TEST IS OK. PARTIAL ONLY @ REAR OF BLDG. ONLY. OK TO BACKFILL TRENCH. 2) C.O SHALL BE LOCATED WHERE THE HORIZONTAL DRAIN EXCEEDS 135 DEGREE. USE A COMBO IN LIEU OF 90 DEGREE. | |
03/09/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HORIZONTAL WASTE FOR LAVATORY EXCEEDS 135 DEGREE A C.O WILL BE REQUIRED WHERE DRAIN EXCEEDS 135 DEGREE 2) SHALL PROVIDE A WATER TEST ON WASTE & VENT SYSTEM. |