Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/25/2016 | MECHANICAL - INTERMEDIATE | Approved | SECOND FLOOR ONLY | |
| 10/20/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FOR FINAL PROVIDE SCREWS IN OSA DUCT 2) PROVIDE A TRAP IN CONDENSATE DRAIN 3) PROVIDE AN OVERFLOW SENSOR |
|
| 11/12/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROVIDE SCREWS IN KITCHEN EXHAUST DUCT AND SEAL JOINTS 2ND FLOOR PRIOR TO SHEETROCK 2) HAVE PLANS REVISED TO SHOW HOW WOOD FRAMED 3) WALL BEHIND HOOD WILL BE MADE NON COMBUSTIBLE 4) OK FOR SHEETROCK 2ND FLOOR |
|
| 11/09/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE SCHEDULE YOUR INSPECTION WHEN SOMEONE WILL BE HERE 2) SYSTEM DOWN, MESSAGES COULD NOT BE CHECKED |