Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T04CM04355
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/29/2005 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* OK TO CLEAR | |
03/28/2005 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* OK TO CLEAR PARTIAL. INSTALL BONDING BUSHING AT SERVICE RISER DUE TO CONCENTRIC K.O | |
03/25/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE REQUIRED TO HAVE A PERMANENT ADDRESS METAL OR PLASTIC SCREWED ON 2) SERVICE REQUIRED TO HAVE 2 GROUND RODS 6' APART WITH A #4 COPPER TIE TO SERVICE |
|
03/24/2005 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* NOT READY |