Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL C OF O |
|
| 03/23/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* EVAP. COOLER NOT OPERATIONAL. EXTEND SEWER VENT 2' ABOVE FRESH AIR INTAKE ON ERU |
|
| 03/17/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* CONNECT SMOKE DETECTOR W/FIRE DAMPER PROVIDE PROPER OVERCURRENT PROTECTION FOR ERU FUSE A/C UNITS. PROVIDE DISCONNECT FOR EVAP. COOLER |
|
| 03/16/2006 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH WORK ON ROOF. PROPER FUSING, DUCT SMOKE DETECTORS, ERU OVERCURRENT PROTECTION, ELEC. DISCONNECTS OK FOR TEMP C OF O |