Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2006 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
| 08/11/2005 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) GAS PRESSURE TEST IS OK FROM METER LOCATION TO BLDG SERVICE 2) YARD WATER LINE FROM BLDG SERVICE TO METER IS OK 3) NOT: APPROVED PLAN CALLS FOR A STRAINER AT BACKFLOW PREVENTOR 4) OK TO BACKFILL TRENCH |