Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/22/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PLEASE PROVIDE A LETTER FOR DELETION OF COMPRESSOR |
|
| 03/19/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20 ALSO REMOVE COMBUSTIBLE. 2. FIXTURES TO BE SECURELY ATTACHED TO GRID 410.16 3. SUPPORT WIRES NEEDED EXIT SIGN 4. FINISH WIRE MOLD/PLUG MOLD SYSTEMS 5. INSTALL MEDICAL LIGHTING 6. VERIFY REQUIREMENTS FOR SMOKE DETECTOR SYSTEM 7. MAINTAIN WORKING CLEARANCES AT AC DISCONNECTS 8. LABEL DISCONNECTS 9. FINISH COOLER 10. INSTALL COMPRESSOR |
|
| 03/03/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |