Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* EXTERIOR CLIP OK TRUSS CONNECTION WAS RESOLVED PREVIOUSLY TO DRY WALL INSTALLATION |
|
| 12/09/2004 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | 1) EXTERIOR CLIP OK TO COVER WALLS (EXT.) 2) SMALL GIRDER EG1 1876 POUNDS ON HANGER END, HUS 48 HOLD 1889 HANGER SPEC'D ON PLAN IS HUS26 ? HAVE ENGINEER CHECK HANGER SIZE, CHECK AT INTERMEDIATE INSPECTION |
|
| 12/07/2004 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) FROM LAST INSPECTION CHANGE OUT (16 SINKERS) TO 16 COMMONS IN GIRDER TO GIRDER CONNECTION, BLK AND NAIL ALL ENDS OF ROOF DECK AND WHERE OSB TURNED PARALELL WITH TRUSSES |
|
| 12/06/2004 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) 1/8" ENDS AND EDGE NAILING REQUIRED ON ROOF. ROOF PANELS BLOCKED 2) NO PLANS/PERMIT ON SITE |
|
| 12/03/2004 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :*/ 1) SEE ALL BLACK MARKS ON ROOF, NAILING AND BLOCKING MISSING THRU OUT 2) NAIL ALL FREIZE BLOCKS TO ROOF 3) USE CORRECT NAILS IN ALL HANGERS 4) EAST SIDE BOTH HEADERS, NOT SHOWN ON PLAN WITH GIRDER BEARING, ON THOSE TWO HEADERS, SIZES NOT ON PLANS 5) BROKEN STUD EAST WALL |