Permit: T04CM04340

Parcel: 123091440


Addresses:

3014 E ADAMS ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/11/2005 FRAMING Approved IVRS - Inspection :*
05/05/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/12/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
04/12/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STUCCO LATH RISER EMBEDDED INTO PLASTER, NEEDS TO BE DONE IN A WORKMANSHIP MANNER, PATIO WALL NO PLASTER BEHIND MASONRY, MISSING EXPANDED LATH AT MASONRY TO FRAME TRANSITIONS, AT REAR PORCH NO WEEP SCREEN BOTH F.F. ARE THE SAME HT. 1/A6 NOT PER DETAIL SUPPLY AN APPROVED DETAIL FOR YOUR SITUATION
2) ZERO GAS PRESSURE
3) FIRE BLOCK AT CEILING KITCHEN WALL (RANGE) LOCATION
4) POWER (ELECTRIC) FOR KITCHEN ISLAND
5) MECH NOT COMPLETED
6) 100,000 BTU NEW FURN IN EXISTING ROOM, NEED COMB/RELIEF SIZED. SIZE RETURN AIR, NOT PLATFORM
7) PLAN CALLS FOR BLACK IRON PIPE GAS, YOU INSTALLED TRAC PIPE. NEED PIPING SCHMATIC
8) OLD GAS LINE AT METER ?
9) NEW GAS PAK NEED CONDENSATE LINE?
10) NEED 10' H20 HEAD D.W. VENT
11) HAVE TRAC PIPE INSTALLATION BOOK WITH PLANS
12) SMOKE DETECTORS IN BEDROOMS
13) VENTING FOR KITCHEN SINK ? NOT ON PLAN
14) NO OVER HANGE ON TOP OF KITCHEN PONY WALL, (COUNTER TOP) OUTLETS BELOW ON THAT WALL
15) ALL J-BOXES TO BE EXPOSED/ACCESSIBLE (KIT)
16) BACKING AT TUB SIDE WALLS, FINISH TUB FRAMING
17) WORKING PRESSURE ON ALL POTABLE H20 LINES
18) WEST WALL AT DOOR FACING NORTH STUD NOT ATTACHED TO WALL (BRICK) LOOSE B/PLATE