Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/05/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/12/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 04/12/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STUCCO LATH RISER EMBEDDED INTO PLASTER, NEEDS TO BE DONE IN A WORKMANSHIP MANNER, PATIO WALL NO PLASTER BEHIND MASONRY, MISSING EXPANDED LATH AT MASONRY TO FRAME TRANSITIONS, AT REAR PORCH NO WEEP SCREEN BOTH F.F. ARE THE SAME HT. 1/A6 NOT PER DETAIL SUPPLY AN APPROVED DETAIL FOR YOUR SITUATION 2) ZERO GAS PRESSURE 3) FIRE BLOCK AT CEILING KITCHEN WALL (RANGE) LOCATION 4) POWER (ELECTRIC) FOR KITCHEN ISLAND 5) MECH NOT COMPLETED 6) 100,000 BTU NEW FURN IN EXISTING ROOM, NEED COMB/RELIEF SIZED. SIZE RETURN AIR, NOT PLATFORM 7) PLAN CALLS FOR BLACK IRON PIPE GAS, YOU INSTALLED TRAC PIPE. NEED PIPING SCHMATIC 8) OLD GAS LINE AT METER ? 9) NEW GAS PAK NEED CONDENSATE LINE? 10) NEED 10' H20 HEAD D.W. VENT 11) HAVE TRAC PIPE INSTALLATION BOOK WITH PLANS 12) SMOKE DETECTORS IN BEDROOMS 13) VENTING FOR KITCHEN SINK ? NOT ON PLAN 14) NO OVER HANGE ON TOP OF KITCHEN PONY WALL, (COUNTER TOP) OUTLETS BELOW ON THAT WALL 15) ALL J-BOXES TO BE EXPOSED/ACCESSIBLE (KIT) 16) BACKING AT TUB SIDE WALLS, FINISH TUB FRAMING 17) WORKING PRESSURE ON ALL POTABLE H20 LINES 18) WEST WALL AT DOOR FACING NORTH STUD NOT ATTACHED TO WALL (BRICK) LOOSE B/PLATE |