Permit: T04CM04316

Parcel: 141015410


Addresses:

10632 E CERULEAN WY


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM04316

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/07/2005 FRAMING Approved IVRS - Inspection :*
01/05/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
1) BANG PLATES H20 SERVICE GARAGE
2) KITCHEN RANGE WIRE SECURE, AND BANG PLATE AT STUD
3) STRAP ACROSS DRYER DUCT
4) BEDROOM NEXT TO LAUNDRY, CIRCUIT NOT COMPLETE SAME BEDROOM, CLOSET LIGHT TO CLOOSE TO MECHANICAL DUCT CEILING
5) CLOSET FLANGE HALL BATH TOO CLOSE TO WALL 12" ROUGH IN
6) NORTH, PORCH MIDDLE POST, WAS INSTALLED AFTER SHEATHING INSPECTION HOW IS IT ATTACHED TO BEAM ?
12/30/2004 FRAMING Not ready for Inspection IVRS - Inspection :*
1) BANG PLATE H20 SERV. LEDGER, GARAGE
2) OVERSPAN STUD KITCHEN BACK SIDE OF TUB
3) SW1 SHEAR GARAGE WEST/NORTH WALLS BLOCK
4) STRAP ACCROSS DRYER DUCT
5) LOOSE OUTLET HALL FROM GARAGE
6) WASHER H20 LINES OUT OF WALL BEDROOM, SAME BEDROOM CLOSET LIGHT, DUCT
7) POCKET DOOR LOSSE, LOOSE PLATE SAME OPENING
8) TOILET FLANGE LESS THAN 12" FROM WALL
9) 04 DROP CEILING RENAIL 2 X 4'S SOUTH BEDROOM, BANG PLATE WIRE CLOSET
10) SECURE CRIPPLE FRONT WINDOW
11) FIRPLACE NOT INSTALLED CANNOT KILL A GAS LINE IN A WALL
12) SHOWER NOT INSTALLED, SHOWER RISER NOT PLUGGED
13) OVERSPAN MASTER CLOSET, AT DOOR BOTH SIDES
14) MIDDLE PORCH POST, STRAP TO BEAM