Permit: T04CM04315

Parcel: 141014650

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T04CM04315

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
11/18/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
11/05/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*/ 1) HAVE PLAN APPROVED BY CITY, AT 3" TRUNK LINE PROBLEM
10/27/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*/ 1) CHANGE OUT 3" SECTION OF PIPE, 2" CLEANOUT FROM LAV TO CLEANOUT 2" TRUNK
10/25/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PLAN CALLS FOR 1 1/4" H20 LINE, 1" INSTALLED 2) CLEANOUT MINIMUM SIZE FOR 3" WASTE LINE IS 2 1/2" YOU HAVE 2" 3) PLEASE LEAVE SAMPLE ON TAPERED BUSHING ON SITE
10/20/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*/ 1) NEED A APPEAL FORM FOR IRC PLUMBING