Permit: T04CM04297

Parcel: 141167520


Addresses:

7800 S SOLOMON AV

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
10/13/2004 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
10/12/2004 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PROVIDE STEEL FOR FOOTERS-SEE DETAIL #2
09/29/2004 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*/ 1) PLAN CALLS FOR FTGS UNDER EACH POST, SIZE 16 X 16 X 12" DEEP, 12" BELOW NATURAL GRADE. I PROBED WITH A LONG SCREWDRIVER, FTG NOT PER PLAN 2) YOU NEED TO UNDER PIN AT EACH POST 3) LIGHT AT NORTH SIDE OF PORCH, YOU NEED A LIST FOR OUTDOORS FIXTURE. FIXTURE J-BOX WIRING NOT TO CODE 4) INSTALL A FIXTURE WITH A MOUNTING BOX OR CONDUIT TO J-BOX THEN ROMEX TO LIGHT WHERE IS THE GROUND WIRE? WHAT TYPE OFF ROMEX DID YOU USE IT'S PAINTED, MUST BE SUNLIGHT RESISTANT 5) OK TO PUT FANS BACK TOGETHER
09/28/2004 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) ILLEGAL ELECTRIC SPLICE AT NORTH END OF PORCH, MUST BE IN APPROVED ELECTRIC BOX 2) OPEN-REMOVE FAN TO VERIFY WIRING 3) EXPOSE FOOTING ON ONE POST TO A DEPTH OF 12" AND 16" WIDE