Permit: T04CM04280

Parcel: 140377060


Addresses:

6992 S MARTLET DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/25/2005 FRAMING Approved IVRS - Inspection :*
02/24/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/22/2005 FRAMING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Check #12 wire at kitchen possible nail, or cut
Strap at dining room dbl top plate requires 16d nails
Nail protect electric at kitchen
Repair shear at laundry
Seal all penetrations from 1st to 2nd floor
Stopped inspection
02/17/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DECK NOT PER PLAN
2) REPAIR SHEAR AT LAUNDRY
3) DBL TOP PLATE NOT CONTINOUS UNDEE GLB
4) FIREBLOCKS MISSING AT KITCHEN
5) COMPLY WITH SECTION R602.6, R602.6.1 AND R602.8
6) NEXT FAILURE WILL RESULT IN A REFEE
02/15/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPAIR SHEAR AT LAUNDRY AT ELECTRIC BOXES AND PLUMBING
2) FIRE BLOCK LANDING AT KITCHEN
3) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR
4) PROVIDE STUD SHOES FOR 2 X 6 STUD BEARING WALL AT HALL BATH AND 16 GAUGE STRAP WITH 16D NAILS AT DBL TOP PLATE
5) LATH NOT COMPLETE AT ENTRY
6) STRAP DBL TOP PLATE AT LAUNDRY WITH 16 GAUGE STRAP
7) FIRE BLOCKS MISSING AT BALLOON WALL
8) STOPPED INSPECTION