Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2006 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* CHECKED FIRE WRAP ON TOP OF HOOD & ON GREASE DUCT. OK TO INSTALL HOOD & BLOWER. |
|
| 06/05/2006 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* FIRE WRAP OK TOP OF HOOD MUST MEET MIN. 18" CLEARANCE ALSO, IF USING FIRE WRAP ON TOP OF HOOD, PROVIDE INSTALL INSTRUCTIONS. |
|
| 05/30/2006 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* REAR WALL OF TYPE 1 HOOD, COMBUSTIBLE IMC 506.3.6 1. OK TO WRAP EX. DUCT ON SITE. 2. WHERE ARE DIMENSIONS FOR EXH. DUCT? APP. PLAN HAS NO DIMENSIONS OR DRAWING. 3. IF DIMENSIONS ARE CORRECT, OK TO START WRAPPING CONTINUES UP INTO CURB. |
|
| 12/30/2005 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :*FIRE WRAP ON GREASE DUCT OK OK TO SET EXHAUST FANS. EXTEND FANS 2" ABOVE EXISTING EVAP COOLERS EXTEND WATER HEATER VENT 3' ABOVE EVAP. COOLER EXTEND SEWER VENTS 2' ABOVE EVAP COOLER IF WITHIN 10' |
|
| 12/23/2005 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :*WATER HEATER REQUIRES 4" VENT PIPE. WHY WAS 6" USED. LARGER VENT CAN CAUSE DRAFTING PROBLEMS & CONDENSATION INSIDE VENT PIPE. NEED TO SEE FIRE WRAP ON GREASE DUCTS. |