Permit: T04CM04237

Parcel: 12703040B


Addresses:

5602 E SPEEDWAY BL

Inspection Status: Denied

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
11/02/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
WATER PIPING FOR RESTROOM CALLS FOR 1/2" CW TO STOOLS, 1" IS INSTALLED FOR FLUSH VALVES, IF FLUSH VALVES ARE REQUIRED PROVIDE REVISED CITY APPROVED WATER ISOMETRIC FOR THIS INSTALLATION WITH CORRECT SIZING.
NOTE: H/C STOOLS ARE TYPICALLY 16"-18" SIDE WALL CLEARANCE FROM FINISH WALL.
11/02/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) IN WALL WATER PIPING FOR WEST RESTROOMS INTALLED PER PLAN
2) WASTE AND VENT SAME AREA OK
3) SHALL SEE COMPLETION OF WATER PIPING OVER HEAD TO SERVICE
05/17/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1 1/4 GAS FROM 2" TO NEW (3) APPLIANCES THRU ANSUL VALVE IN EXISTING KITCHEN OK
CONTRACTOR SHALL DO TIE IN & VERIFY NO LEAKAGE AT 2" PROVIDE SHUT OFF VALVES AND CORRECT FLEXES AT APPLIANCES.
05/16/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/08/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
INTERMEDIATE IN NEW BAR AREA OK
02/14/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/31/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NEW BAR AREA WILL REQUIRE REVISED APPROVED PLAN
09/27/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) GAS PRESSURE TEST IS OK
2) OVERHEAD WATER DISTRIBUTION IN PLUMBING WALLS ONLY IN KITCHEN AREA