Permit: T04CM04237

Parcel: 12703040B


Addresses:

5602 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
10/23/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
CONTINUATION OF 4" BUILDING SEWER TO EXISTING WATER TEST OK
1. PROVIDE TRACER WIRE
WASTE & VENT THRU ROOF WATER TEST OK
10/12/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
ROUGH SOIL TOILET RMS THROUGH 2 WAY CO OK TO COVER
CREECH'S PLUMBING CONTRACTOR
10/11/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
ROUGH PLUMBING IN NEW RESTROOM LOCATION INSIDE BUILDING IS OK EXCEPT FOR FLOOR CLEANOUT. USE BRASS BODY FRANK PATTERN CLEANOUT FITTING OR INSTALL IN WALL AS SPECIFIED. TRACER WIRE REQUIRED OUTSIDE. 2" LAV WASTE OUTSIDE AND 4" SEWER AT 2-WAY CLEANOUT IS NOT PROPERLY SLOPED. ALSO VENTING NOT PER PLAN.
05/16/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
- WATER TEST NEW FLOOR SINK & HAND SINKS IN EXISTING KITCHEN THRU ROOF & TO EXISTING VENT CONNECTION OK
- WATER PIPING SAME OK
1. PENDING SECURING PEX AT 32" INTERVALS ABOVE CEILING.
02/14/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) REVISED PLAN DATED 2/9/06 FROM PAUL ERIC ? ON SITE WILL NEED CITY APPROVAL. THIS PLAN SHALL ACT AS RED LINE ON SITE.
2) WATER TEST WASTE AND VENT THRU ROOF BAR AREA OK
3) WATER DISTRIBUTION IN WALL BAR AREA AIR TEST OK
4) NEED TO SEE CONTINUATION OF HOT AND COLD SUPPLY TO BAR AREA
08/22/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) WATER TEST SOIL UNDERGROUND EXTERIOR OF BUILDING OK
08/09/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) SOIL WATER TEST IS OK
2) NOTE: THIS INSPECTION IS FOR GREASE WASTE LINE ONLY
3) OK TO BACK FILL TRENCH
08/08/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) NOT READY FOR INSPECTION