Permit: T04CM04237

Parcel: 12703040B


Addresses:

5602 E SPEEDWAY BL

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/19/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. FILL UNUSED OPENINGS IN PANES
2. SECURE CABLE TO CABINET AND CABLES ABOVE PANEL
3. PLANS CALL FOR 2 LIGHT FIXTURE ON WALLS WE ONLY HAVE ONE.
4. CANNOT DETERMINE STRAPPING FOR FIXTURES IN WALLS.
5. SWITCHES APPEAR TO BE NEW OPEN WALLS AT SWITCHES FOR INSPECTION.
6. SUPPORT VDV CABELING UP OFF OF GRID 725.6
7. SUPPORT M/C CABLE WITHIN 12' OF CANS AND AS
PER 300.11

DO NOT PROCEED UNTIL ITEMS ARE CORRECTED.
04/19/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK C OF O FOR BAR AREA & LOBBY (WAITING AREA)
OK ABOVE CEILING J-BOXES FIXTURES
OK REVISIONS PER PLAN
03/28/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE UNAPPROVED EXTENDER RING 314.20 FLESH ON COMBUSTABLES -- METAL NOT APPROVED.
2. NEED PLANS REVISED FOR WORK INSTALLED.
01/17/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK ? IN BOX
01/13/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*OK KITCHEN ONLY ??? SUBJECT TO OTHER INSPECTOR
01/11/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*