Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FILL UNUSED OPENINGS IN PANES 2. SECURE CABLE TO CABINET AND CABLES ABOVE PANEL 3. PLANS CALL FOR 2 LIGHT FIXTURE ON WALLS WE ONLY HAVE ONE. 4. CANNOT DETERMINE STRAPPING FOR FIXTURES IN WALLS. 5. SWITCHES APPEAR TO BE NEW OPEN WALLS AT SWITCHES FOR INSPECTION. 6. SUPPORT VDV CABELING UP OFF OF GRID 725.6 7. SUPPORT M/C CABLE WITHIN 12' OF CANS AND AS PER 300.11 DO NOT PROCEED UNTIL ITEMS ARE CORRECTED. |
|
| 04/19/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK C OF O FOR BAR AREA & LOBBY (WAITING AREA) OK ABOVE CEILING J-BOXES FIXTURES OK REVISIONS PER PLAN |
|
| 03/28/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE UNAPPROVED EXTENDER RING 314.20 FLESH ON COMBUSTABLES -- METAL NOT APPROVED. 2. NEED PLANS REVISED FOR WORK INSTALLED. |
|
| 01/17/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK ? IN BOX |
|
| 01/13/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*OK KITCHEN ONLY ??? SUBJECT TO OTHER INSPECTOR | |
| 01/11/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |