Permit: T04CM04237

Parcel: 12703040B


Addresses:

5602 E SPEEDWAY BL

Inspection Status: Partial Approval

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
01/10/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK WALLS AND CEILING IN BATHROOMS
01/11/2006 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
1. PANEL COVER TO BE ADDRESSED ON OUTSIDE OF COVER ALSO NEED HIGH LEG MARKINGS ON OUTSIDE OF COVER. BOND PANEL ENCLOSURE
2. INSIDE WALK IN BOX - JUNCTION BOX TO USE CORRECT SIDED FITTINGS OR ADAPTORS. ALSO SEAL AS PER 300.7
3. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING 250.8
4. ALL DUPLEX RECEPTACLES TO BE GFCI PROTECTED IN KITCHEN 210.8 (C)
5. PLEASE INSTALL REJECTION PINS AND LABEL DISCONNECTS (PANEL VOLTAGE)
6. IDENTIFY GROUNDING CONDUCTOR
7. BONDING JUMPER TO BE SIZED PER 250.102 & 250.66
8. BOND DISCONNECT ENCLOSURE
9. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN SERVICE EQUIP.