Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04CM04237

Parcel: 12703040B


Addresses:

5602 E SPEEDWAY BL

Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/02/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
FINISH PREVIOUS ITEMS
12/19/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/29/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLANS NOT REFLECTIVE OF ALL WORK INSTALLED.
2. OPEN WALLS AND CEILINGS AS DIRECTED PREVIOUS INSPECTION.
11/16/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. OPEN WALLS FOR INSPECTION -- COVERED WITHOUT INSPECTION.
2. OPEN CEILING TILE TO INSPECT.
3. NO REVISED PLANS ON SITE.
4. PLEASE VERIFY WHO QUALIFIED ELECTRICAL IS
03/13/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ABOVE CEILING OVER BAR
03/08/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK LIGHTS OVER BAR (20)
1. VDV CABLING TO BE AS PER 725.2 & 6, 800.2 & 6
01/31/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROTECT M/C CABLE AT STUDS
2) OK BAR WALL
11/21/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*NEED TO SEE CONNECTION TO COUNTER IN CENTER OF ROOM. OK WALLS
11/16/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*SUPPORT CONDUITS ABOVE PANEL
LB TO BE ACCESSIBLE
PROTECT CABLES AT STUDS
PLEASE PROVIDE PAPERWORK FOR LISTING OF M/C CONNECTORS
OK WALLS EXCEPT PANEL WALL SUBJECT TO PAPERWORK VERIFYING CONNECTORS.