Permit: T04CM04233

Parcel: 140323430

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
12/23/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1) FROM LAST INSPECTION A/C LINE SET, FHA STRAP BOTH PLATES LIVING ROOM DBL TOP PLATE
2) INSTALL FIRE STOPS AT H20 HTR FLUE AT FLOOR, CEILING LINES
12/21/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) H20 LINE PEX AT H20 HTR FLUE NEED 6" CLEARANCE
2) H20 HTR FLUE TO BE AT MAXIMUM 60 DEGREE AT OFF SET, INSTALL FIRE STOPS AT FLOOR/CEILING MAINTAIN 1' CLEARANCE TO COMBUSTIBLE
3) PLATE FHA BOTH PLATES, LINE SET 1ST FLOOR TOP PLATE
4) BANG PLATE PEX LINE IN POWDER ROOM
12/20/2004 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/17/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*