Permit: T04CM04233

Parcel: 140323430

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM04233

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
12/21/2004 FRAMING Approved IVRS - Inspection :*
12/20/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PEX OUTSIDE OF WALL WATER ?
2) W/H VENT REQUIRES 1" TO COMBUSTIBLES
3) PEX MUST BE 6" TO B VENT W/H
4) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF PLATE SURFACE
5) 13/D6 NOT COMPLIED WITH TOE NAILS DO NOT COUNT
6) FIREBLOCK STAIR BELOW WINDOW
7) FIRESTOP W/H "B" 2ND FLOOR
8) WATCH 1" CLEARANCE 6 PLACES
12/17/2004 FRAMING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED ON SITE BY MARK
2) NOT COMPLETE ENOUGH TO INSPECT