Permit: T04CM04231

Parcel: 121083090


Addresses:

6226 E PIMA ST #100


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T04CM04231

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/10/2005 MECHANICAL - FINAL Approved IVRS - Inspection :* APPROVED OK FOR FINAL C OF O
03/09/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* A/C UNITS ARE OVERFUSED. SEE DATA PLATE ON UNITS FOR PROPER FUSING. PROVIDE FRESH AIR INTAKES AS PER PLANS. AUX. DUCT SMOKE DETECTOR INDICATORS NOT ACTIVATED.