Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM04231
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/10/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL | |
03/09/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS. 2) PANEL SCHEDULES TO BE PERMANENT. 3) JUNCTION BOXES AT EXHAUST FANS TO BE GROUNDED-ROOF. 4) TIGHTEN LOOSE SEAL TITE FITTINGS-ROOF. |