Permit: T04CM04223

Parcel: 115202570


Addresses:

1991 W ELM ST #02

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/07/2005 BUILDING - FINAL Approved IVRS - Inspection :*
10/05/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL BONDING JUMPER ACCROSS NON-METALLIC AC BELLOWS ON ROOF
2) CONTINUE A/C CONDENSATE TO GROUND AND INSTALL DRY WALL TO RUN INTO
3) IF UTILITY SINK IS TO BE DELETED REMOVE ALL SUPPLY AND DRAIN LINES
4) BREAK OFF LITTLE BOLT ON HOSE BIB ANTI-SIPHON DEVICE
5) MAINTAIN MINIMUM 6" CLEARANCE SIDING TO DIRT
6) INSTALL H20 HEATER IN METAL ENCLOSURE
7) CUT SEWER CLEANOUT TO GRADE AND COMPLETE GRADING
10/03/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*