Permit: T04CM04220

Parcel: 122173610


Addresses:

3138 E ADAMS ST #02

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
03/09/2005 BUILDING - FINAL Approved IVRS - Inspection :*
1) HOLE IN DRYER EXHAUST
03/07/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POST ADDRESS
2) PAINT ALL ROOF VENTS
3) PROVIDE ACCESS TO ROOF
4) UNABLE TO ENTER TO INSPECT ALL EXTERIOR DOORS LOCKED
02/28/2005 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) CUT OFF CLEANOUTS TO GRADE
2) INSTALL 90 DEGREE ELBOW ON T & P AND CONDENSATE
3) NEED ANTI-SYPHON ON HOSE BIB
4) 3" VENT MINIMUM 12" ABOVE ROOF
5) SECURE FLEX AT A/C ROOF UNIT
6) MAXIMUM FUSE SIZE IS 60/60, CLEAR AMPACITY IS 51-54 CIRCUIT BREAKER IS 50/50 INSTALLED, VERIFY WIRE SIZE IS #6 CU. THEN OK TO INSTALL 60/60 BREAKER
7) CHECK ALL RECEPTACLES SOME ARE LOOSE