Permit: T04CM04209

Parcel: 11308148A

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/17/2005 FRAMING Approved IVRS - Inspection :*
03/11/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TRUSS H2.5 MUST HAVE NAILS IN EVERY HOLE CATCH BOTH TOP PLATES
2) DBL STUD NEEDED AT ALL ALTERNATIVE HOLDOWNS 16D EVERY HOLE
3) INSULATE BEHIND TUB WALLS
4) FASTEN MESH 6" ON CENTER TOP AND BOTTOM PLATES
5) SECURE MESH AROUND WINDOWS
6) MAKE UP REFRIDGERATOR WATER LINE IN BOX